Electrical installation
4.8 Signal connections
Motor temperature sensor interface
Table 4- 24
Motor temperature sensor interface
Pin
Designation
14
T1 MOTOR
15
T2 MOTOR
Max. connectable cross-section: 1.5 mm²
Power supply
Table 4- 25
Power supply
Pin
Designation
9
+24 V OUT
28
GND
1
+10 V OUT
2
GND
31
+24 V IN
32
GND IN
35
+10 V OUT
36
GND
Max. connectable cross-section: 1.5 mm²
GND: reference potential
1)
X128: Serial interface (RS485)
Table 4- 26
Serial interface (RS485) X128
Terminal
Designation
1
0 V
2
RS485P
3
RS485N
4
GND
5
--
Max. connectable cross-section: 1.5 mm²
92
Positive input for motor temperature sensor
Type: PTC, KTY sensor, Thermo-Click
Negative input for motor temperature sensor
1)
Power supply output
24 VDC, max. 200 mA
Reference potential of the power supply/internal electronics ground
Power supply output
10 VDC ±0.5 V, max. 10 mA
Reference potential of the power supply/internal electronics ground
Power supply input
18 ... 30 VDC, max. 1500 mA
Reference potential of the power supply input
Power supply output
10 VDC ±0.5 V, max. 10 mA
Reference potential of the power supply/internal electronics ground
Technical data
Ground reference
Receive and transmit +
Receive and transmit -
Cable shield
not used
Technical data
Technical data
Operating Instructions, 12/2014, A5E32923362A