Advertisement

Operation
6.6 PROFIenergy profile for PROFINET
Transition to the energy-saving mode from the PROFIdrive operating state (S4)
If you set p5611.2 = 1, you permit the transition to the energy-saving mode from the
PROFIdrive operating state (S4).
You can select the following:
● p5611.1 = 1
With the transition to the energy-saving mode, the inverter issues an OFF1 command and
enters the start-inhibit state (S1).
● p5611.1 = 0
You can use p5614 to interconnect a signal source that switches the inverter off and
places it in the start-inhibit state (S1).
PROFIenergy measured values
PROFIenergy
Measured value
ID
Name
34
Active power
166
Power factor
200
Active energy import
206
Accuracy
Unit
Domain
Class
1
12
W
1
12
1
2
11
Wh
SINAMICS source parameters
Number
Name
r0032
Active power smoothed
r0038
Smoothed power factor
r0039[1]
Energy accepted
Operating Instructions, 12/2014, A5E32923362A
Value range
r2004
0 ... 1
-
Inverter cabinet units