Extend Telegrams And Change Signal Interconnection - Siemens Sinamics G120P Operating Instructions Manual

Converter cabinet units 110 kw - 400 kw
Hide thumbs Also See for Sinamics G120P:
Table of Contents

Advertisement

Operation
6.5 PROFIdrive profile for PROFIBUS and PROFINET
Status word 3 (ZSW3)
Status word 3 has the following standard assignment. See also function diagram 2456.
Bit Value Significance
0
1
DC braking active
1
1
|n_act| > p1226
2
1
|n_act| > p1080
3
1
i_act ≧ p2170
4
1
|n_act| > p2155
5
1
|n_act| ≦ p2155
6
1
|n_act| ≧ r1119
7
1
DC-link voltage ≦ p2172
8
1
DC-link voltage > p2172
9
1
Ramping completed
10 1
Technology controller output at lower limit
11 1
Technology controller output at upper limit Technology controller output > p2291
12
Reserved
13
Reserved
14
Reserved
15
Reserved
6.5.1.3

Extend telegrams and change signal interconnection

When you have selected a telegram, the inverter interconnects the corresponding signals
with the fieldbus interface. Generally, these interconnections are protected so that they
cannot be changed. With the appropriate inverter settings, these interconnections can be
changed.
Extending a telegram
Every telegram can be extended by "attaching" additional signals.
192
Description
--
Absolute actual speed > stationary state
detection
Absolute actual speed > minimum speed
Actual current ≥ current threshold value
Absolute actual speed > speed threshold
value 2
Absolute actual speed < speed threshold
value 2
Speed setpoint reached
Actual DC-link voltage ≦ threshold value
Actual DC-link voltage > threshold value
Ramp-function generator is not active.
Technology controller output ≦ p2292
Operating Instructions, 12/2014, A5E32923362A
Signal interconnection
in the inverter
p2051[3] = r0053
Inverter cabinet units

Advertisement

Table of Contents
loading

Table of Contents