Operation
6.10 Operation with the IOP
3.
4.
5.
6.
7.
To deactivate the write protection function, perform the same procedure as above but select
"0: Deactivate write protection".
334
Select the "Search for number" entry in the "Parame-
ters" menu.
Enter "07761" and press "OK".
The parameter from the "All parameters" menu is
displayed automatically on the screen. The parameter
for the write protection is emphasized. Note that the
current status of the write protection function is dis-
played under the parameter name. Press "OK" to
select the parameter.
Select "1: Activate write protection" to activate the
write protection function.
Press "OK" to confirm your selection.
The display returns to the "All parameters" screen and
the parameter for the write protection is emphasized
to specify the status of the function as active.
Press the "Esc" key twice to return to the "Status"
screen.