Advertisement

Diagnostics
5.2 Diagnostics using LEDs
LED
Color
Red/
green
Orange
Green/
orange
or
red/
orange
Green/
orange
or
red/
orange
COM
PROFIdrive
cyclic
operation
Green
Red
OPT
Green
Red
242
Display
Description, cause, remedy
Flashing light
Control Unit is ready. However, software licenses are missing.
0.5 Hz
Remedy: Obtain licenses.
Flashing light
Updating the firmware of the DRIVE-CLiQ components
0.5 Hz
Flashing light
DRIVE-CLiQ component firmware update complete. Wait for
2 Hz
POWER ON for the components in question.
Remedy: Carry out a POWER ON for the components in ques-
tion
Flashing light
Control Unit detection via DCP flashing
1 Hz
Remark:
Both options depend on the LED status when component
recognition is activated via DCP.
Flashing light
LED-supported detection of Control Unit is activated
2 Hz
(p0124[0] = 1).
Remark:
Both options depend on the LED status when component
recognition is activated via p0124[0] → 1.
Off
Cyclic communication has not (yet) taken place.
Remark:
PROFIdrive is ready for communication when the Control Unit is
ready (see LED RDY).
Continuous light
Cyclic communication is taking place.
Flashing light
Full cyclic communication has not yet taken place.
0.5 Hz
Possible causes:
Flashing light
Bus fault, incorrect parameterization/configuration
0.5 Hz
Remedy: Adapt configuration between master/controller and
CU.
Flashing light
Cyclic bus communication has been interrupted or could not be
2 Hz
established.
Remedy: Correct fault.
Off
Electronics power supply is missing or outside permissible toler-
ance range.
Component is not ready.
Option board not installed or no associated drive object has
been created.
Remedy: Check power supply and/or component
Continuous light
Option board is ready.
Flashing light
Depends on the Option Board used.
0.5 Hz
Continuous light
Depends on the Option Board used.
The controller is not transferring any setpoints.
During isochronous operation, no global control (GC) or a
faulty global control (GC) is transferred by the controller.
Only possible for CU320-2 PN: "Shared Device" is selected
(p8929=2) and only one controller connected.
Commissioning Manual, 12/2018, 6SL3097-5AA10-0BP0
.