Smart Line Modules booksize 5 kW and 10 kW

Table 5- 7
Meaning of the LEDs at the Smart Line Modules 5 kW and 10 kW
LED
Color
READY
Green
Yellow
Red
DC LINK
Yellow
Red
Commissioning with Startdrive
Commissioning Manual, 12/2018, 6SL3097-5AA10-0BP0
Description, cause
DRIVE-CLiQ communication is being established.
At least one fault is present in this component.
Note:
LED is controlled irrespective of the corresponding messages
being reconfigured.
Firmware is being downloaded.
Firmware download is complete. Wait for POWER ON.
Component detection via LED is activated (p0124).
Note:
Both options depend on the LED status when module recog-
nition is activated via p0124 = 1.
State
Description, cause
Off
Electronic power supply is missing or outside permissi-
ble tolerance range.
Continu-
Component is ready to operate.
ous light
Continu-
Pre-charging not completed.
ous light
Bypass relay dropped out
EP terminals not supplied with 24 VDC.
Continu-
Overtemperature
ous light
Overcurrent
Off
Electronic power supply is missing or outside permissi-
ble tolerance range.
Continu-
DC link voltage within permissible tolerance range.
ous light
Continu-
DC link voltage outside permissible tolerance range.
ous light
Line supply fault.
Diagnostics
5.2 Diagnostics using LEDs
Remedy
Remedy and acknowledge
fault.
Carry out a POWER ON
Remedy
Diagnose fault (via output
terminals) and
acknowledge it (via input
terminal)
Check the line voltage.
245