Function Diagrams And Parameters - Siemens SINAMICS S120 Commissioning Manual

With startdrive
Hide thumbs Also See for SINAMICS S120:
Table of Contents

Advertisement

3. Interconnect the "Standstill detection threshold" (p1225) signal sink for the standstill
detection.
4. Enter the speed threshold for standstill detection in the "Threshold" (p1226[0]) field.
5. Enter the delay time for pulse suppression in the "Delay time" (p1228) field.
6. Enter the monitoring time for standstill detection in the "Monitoring time" (p1227) field.
This step is omitted if the deceleration ramp has been switched off in step 2.
7. Click "OK" to confirm the entries.
The dialog closes.
Configuring disable standstill detection
If you want to disable standstill detection, proceed as follows:
1. Select the "ON" entry in the "Disable standstill detection" drop-down list.
2. Enter the deceleration time for closing the brake at standstill in the "Disable standstill
detection" (p1276) input field below the graphic.
4.11.4

Function diagrams and parameters

Function diagrams (see SINAMICS S120/S150 List Manual)
• 2701
• 2704
• 2707
• 2711
Overview of important parameters (see SINAMICS S120/S150 List Manual)
• r0108.14
• r0899.0...15
Standstill monitoring
• r0060
• r0063
• r0063[0...2]
Commissioning with Startdrive
Commissioning Manual, 12/2018, 6SL3097-5AA10-0BP0
Brake control - Simple brake control (r0108.14 = 0)
Brake control - Extended brake control,
stationary state detection (r0108.14 = 1)
Brake control - Extended brake control, open/close brake
(r0108.14 = 1)
Brake control - Extended brake control,
signal outputs (r0108.14 = 1)
Drive objects, function module;
Extended brake control
CO/BO: Status word, sequence control
CO: Speed setpoint before the setpoint filter
CO: Actual speed value smoothed
(for servo)
CO: Actual speed value
(for vector)
Commissioning
4.11 Configuring brake control
235