4.5.4.3

Assigning an IP address

Adapting the IP address in the drive
Before you can go online on a drive via PROFINET, you must assign the PROFINET
interface of the drive a suitable IP address.
● When supplied, the PROFINET interface of the drive has no IP address.
● If a cyclic connection already exists from SINAMICS to the controller, it is no longer
possible to assign an IP address.
The PROFINET interface has already been assigned an IP address and subnet mask in the
project:
● IP address: 192.168.0.1
● Subnet mask: 255.255.255.0
The IP address and subnet mask lie in the subnet of an S71500 control, which simplifies
networking the control system and drive.
Requirement
An online connection to the drive exists, and you have made a search for the drives under
Online access in the appropriate interface with "Update accessible devices".
The device is displayed.
Procedure
To assign an IP address, proceed as follows:
1. Double-click "Online & Diagnostics" under "Online access" in the project navigator.
2. Double-click the "Functions" entry in the secondary navigation of the working area.
3. Double-click the "Assign IP address" entry.
Figure 4-43
4. Enter an IP address that matches your project.
5. Enter an appropriate subnet mask.
Commissioning with Startdrive
Commissioning Manual, 12/2018, 6SL3097-5AA10-0BP0
Assigning an IP address
4.5 Establishing an online connection to the drive
Commissioning
135