Diagnostics
5.2 Diagnostics using LEDs
Table 5- 26
Meaning of the OPT LED on the Control Unit
LED
Color
OPT
–
Green
Red
Orange
5.2.3.6
Voltage Sensing Module VSM10
Table 5- 27
Meanings of the LEDs on the Voltage Sensing Module VSM10
LED
Color
READY
–
Green
Orange
Red
256
Status
Description, cause
OFF
The electronics power supply is missing or outside the per-
missible tolerance range.
CBE20 either defective or not inserted.
Continu-
CBE20 is ready and cyclic communication is taking place.
ous light
Flashing
CBE20 is ready but cyclic communication is not running.
light
Possible causes:
0.5 Hz
Communication is being established.
•
At least one fault is present.
•
Continu-
Cyclic communication via PROFINET has not yet been
ous light
established. However, non-cyclic communications are pos-
sible. SINAMICS is waiting for a parameteriza-
tion/configuration telegram.
Flashing
The firmware update into the CBE20 has been completed
light
with an error.
0.5 Hz
Possible causes:
The memory card for the control unit is defective.
•
The CBE20 is defective.
•
In this state CBE20 cannot be used.
Flashing
There is a communications error between the Control Unit
light
and the CBE20.
2 Hz
Possible causes:
The CBE20 was withdrawn after booting.
•
The CBE20 is defective.
•
Flashing
Firmware of the CBE20 currently being updated.
light
0.5 Hz
Status
Description, cause
Off
The electronics power supply is missing or outside the per-
missible tolerance range.
Continu-
The component is ready for operation. Cyclic DRIVE-CLiQ
ous light
communication is taking place.
Continu-
DRIVE-CLiQ communication is being established.
ous light
Continu-
This component has at least one fault.
ous light
Note:
LED is controlled irrespective of the corresponding messag-
es being reconfigured.
Commissioning with Startdrive
Commissioning Manual, 12/2018, 6SL3097-5AA10-0BP0
Remedy
–
–
–
–
–
Correctly insert the
board, if required,
replace.
–
Remedy
–
–
–
Remove and
acknowledge the fault.