FusionModule2000 Smart Modular Data Center
Installation Guide (2000 mm High Cabinets, Dual-Row
Aisle Containment, 208 V)
Procedure
Step 1 Determine the mounting holes for the rack environment unit in the cabinet based on the
engineering layout diagram and install floating nuts.
Step 2 Secure the rack environment unit to the cabinet by tightening the M6 screws on the left and
right mounting ears clockwise.
Figure 8-16 Installing a rack environment unit
----End
8.7 Installing Monitoring Components on a Control
Skylight
Monitoring components should be installed in the appropriate holes on the control skylight.
Issue 01 (2017-07-30)
If a ground copper bar is installed on the top of the rack rail, install a rack environment
unit at the 40 U position. A cable manager should be installed between the rack
environment unit and the ground bar.
If no ground copper bar is installed on the top of the rack rail, install a rack environment
at the top of the rack rail.
Huawei Proprietary and Confidential
Copyright © Huawei Technologies Co., Ltd.
8 Installing Monitoring Devices
133