Huawei FusionModule2000 Installation Manual page 179

Smart modular data center 2000 mmhigh cabinets, dual-row aisle containment, 208 v
Hide thumbs Also See for FusionModule2000:
Table of Contents

Advertisement

FusionModule2000 Smart Modular Data Center
Installation Guide (2000 mm High Cabinets, Dual-Row
Aisle Containment, 208 V)
Procedure
Step 1 Mark management areas based on the air conditioner layout.
Step 2 Assign T/H sensors by area.
Assign three T/H sensors to each area as follows:
1.
2.
3.
Issue 01 (2017-07-30)
Scenario 1: There is an odd number of IT cabinets between air conditioners. In this
scenario, categorize the cabinet in the middle of the two air conditioners to the area of
the air conditioner on the left (front view), as shown in
Components in the background with the same color belong to the same area.
Figure 8-65 Categorizing an odd number of cabinets
Scenario 2: There is an even number of IT cabinets between air conditioners. In this
scenario, categorize the cabinets evenly, as shown in
Components in the background with the same color belong to the same area.
Figure 8-66 Categorizing an even number of cabinets
Assign the first T/H sensor to the cabinet furthest from the air conditioner, as shown by
(1) in
Figure 8-67
and
Figure
If there is the same number of cabinets on the two sides of an air conditioner (as shown by air
conditioner 3 in
Figure 8-67
left side of the air conditioner.
Assign the second T/H sensor to the cabinet furthest from the other side of the air
conditioner, as shown by (2) in
Assign the third T/H sensor to the cabinet that is between the first T/H sensor and the air
conditioner and near the air conditioner, as shown by (3) in
Huawei Proprietary and Confidential
Copyright © Huawei Technologies Co., Ltd.
8-68.
and
Figure
8-68), preferentially deploy a T/H sensor to the cabinet on the
Figure 8-67
and
8 Installing Monitoring Devices
Figure
8-65.
Figure
8-66.
Figure
8-68.
Figure 8-67
and
Figure
8-68.
170