Determine a pipe connection method based on site pipe materials.
Figure 3-26 Connecting a humidifier water inlet pipe
(1) Rigid pipe: 1/2-inch BSPT, external
thread, made of PP-R, C-PVC, or other
materials
(3) Hose clamp

3.2.5 Drainpipe

A drainpipe should be able to withstand a temperature greater than 85° C. Otherwise, pipe
deformation may occur (for equipment configured with a humidifier).
A drainpipe can be connected in two ways:
Determine a pipe connection method based on site pipe materials.
Issue 01 (2017-07-30)
Rigid pipe: Prepare rigid pipes shown by method A in
Hose: Prepare hoses and pagoda connectors shown by method B in
Components inside the dashed-line boxes are ports on the equipment. Component 3 is mandatory. Other
components are subject to engineering procurement.
Top pipe routing: For the connection method of the water pump drainpipe, see method A
in
Figure
3-27.
Bottom pipe routing: See methods B and C in
Huawei Proprietary and Confidential
Copyright © Huawei Technologies Co., Ltd.
3 Hardware Installation Preparations
Figure
3-26.
Figure
(2) Pagoda connector: 1/2–inch BSPT,
connected to a pipe with external threads
(4) Hose: made of EPDM or other
materials
Figure
3-27.
3-26.