5.2.1 Installing a Lower Mounting Kit for the End Door

Context
The lower mounting kit for the end door is required only when 2000 mm high cabinets are
placed at an end of the aisle containment, and can be obtained from the end door fitting bag.
The lower mounting kit for the end door is used to seal the bottom of 2000 mm high cabinets
placed at an end of the aisle containment, and consists of five components, as shown in
5-12.
Figure 5-12 Assembled lower mounting kit for the end door
(1) Side sealing plate
Procedure
Step 1 Take the five components of the lower mounting kit for the end door out of the end door
fitting bag, and assemble four of them into front and real sealing plates with the same width as
the cabinet, as shown in
Issue 01 (2017-07-30)
The front and rear sealing plates are each assembled by two components. The length after assembly can
be 600 mm or 800 mm.
Figure
(1) in
Figure 5-13
shows the individual front and rear sealing plates.
(2) in
Figure 5-13
shows the assembled front and rear sealing plates for 600 mm wide cabinets.
(3) in
Figure 5-13
shows the assembled front and rear sealing plates for 800 mm wide cabinets.
Huawei Proprietary and Confidential
Copyright © Huawei Technologies Co., Ltd.
(2) Front or rear sealing plate
5-13.
5 Installing the Contained Aisles