Table 5-4 Door box placement faults
Fault Type
Door box tilted with a
V-shaped gap
Door box tilted with a
Λ-shaped gap
1.
Issue 01 (2017-07-30)
Figure 5-34
shows a tilted door box. Turn the M6 door box screw in the leveling corner
piece furthest from the door frame clockwise to lift the door box until the V-shaped gap
disappears, as shown by (1) in
Figure 5-34 V-shaped gap
Huawei Proprietary and Confidential
Copyright © Huawei Technologies Co., Ltd.
Possible Cause
The top front and rear of the
cabinet are not on the same
level. Usually the front is
higher than the rear.
The top front and rear of the
cabinet are not on the same
level. Usually the front is
lower than the rear.
Figure
5-35.
5 Installing the Contained Aisles
Measure
For details about the
adjusting method, see
7.1.
For details about the
adjusting method, see
7.2.
Step
Step
105