Figure 3-25 Oil trap and inverted traps (unit: mm)
Table 3-3 Specifications for oil traps and inverted traps
No.
1
2
3
NOTE

3.2.4 Humidifier Water Inlet Pipe

The humidifier water inlet pipe can be connected in two modes:
Issue 01 (2017-07-30)
Name
Copper Pipe Outer
Diameter and
Thickness
Oil trap
19.1 mm x 1.2 mm
Gas pipe
19.1 mm x 1.2 mm
inverted
trap
Liquid
16.0 mm x 1.0 mm
pipe
inverted
trap
After the traps are made, verify that the surface is smooth and even, and that there is no bur at the
pipe ends.
Pipe bends not marked in the figure are 90° .
The bend tolerance is ± 1 mm.
Huawei Proprietary and Confidential
Copyright © Huawei Technologies Co., Ltd.
3 Hardware Installation Preparations
Technical Requirements
The flaring inner diameter of the copper
pipe is 19.1 mm, and the necking outer
diameter are 16.0 mm.
Inner diameter of flared ends of the
copper pipes 19.1 mm.
Inner diameter of flared ends of the
copper pipe: 16.0 mm.
35