Section 6
Wide area measurement system
IEC140000119 V2 EN-US
Figure 35: Multiple instances of PHASORREPORT blocks
Figure
36
in the bottom of each function block. For each instance, there are three separate ANALOGREPORT
blocks capable of reporting up to 24 Analog signals (8 Analog signals in each ANALOGREPORT
block). These can include for example transfer of active and reactive power or reporting the
milliampere input signals to the PDC clients as defined in IEEE C37.118 data frame format.
IEC140000120 V2 EN-US
Figure 36: Multiple instances of ANALOGREPORT blocks
Figure
37
in the bottom of each function block. For each instance, there are three separate BINARYREPORT
blocks capable of reporting up to 24 Binary signals (8 Binary signals in each BINARYREPORT block).
These binary signals can be for example dis-connector or breaker position indications or internal/
external protection alarm signals.
98
shows both instances of ANALOGREPORT function blocks. The instance number is visible
shows both instances of BINARYREPORT function blocks. The instance number is visible
© Copyright 2017 ABB. All rights reserved
IEC140000119-2-en.vsd
IEC140000120-2-en.vsd
1MRK 511 401-UUS F
Bay control REC670