Section 14
Control
Table 45: Description of the input-output relationship
VALID
0
1
1
1
1
14.8.3
Setting guidelines
The function does not have any parameters available in the local HMI or PCM600.
14.9
Single point generic control 8 signals SPC8GAPC
14.9.1
Identification
Function description
Single point generic control 8 signals
14.9.2
Application
The Single point generic control 8 signals (SPC8GAPC) function block is a collection of 8 single
point commands that can be used for direct commands for example reset of LED's or putting IED
in "ChangeLock" state from remote. In this way, simple commands can be sent directly to the IED
outputs, without confirmation. Confirmation (status) of the result of the commands is supposed
to be achieved by other means, such as binary inputs and SPGAPC function blocks.
14.9.3
Setting guidelines
The parameters for the single point generic control 8 signals (SPC8GAPC) function are set via the
local HMI or PCM600.
Operation : turning the function operation Enabled / Disabled .
There are two settings for every command output (totally 8):
402
OPEN
-
0
1
0
1
IEC 61850
identification
SPC8GAPC
PSTO is the universal operator place selector for all control functions. Even if PSTO
can be configured to allow LOCAL or ALL operator positions, the only functional
position usable with the SPC8GAPC function block is REMOTE.
© Copyright 2017 ABB. All rights reserved
CLOSE
Value
-
0
0
0
0
1
1
2
1
3
IEC 60617
ANSI/IEEE C37.2
identification
device number
-
-
1MRK 511 401-UUS F
POSITION
Description
Intermediate
Intermediate
Open
Closed
Bad State
SEMOD55398-5 v5
SEMOD176448-1 v3
SEMOD176456-2 v3
SEMOD176511-4 v7
SEMOD176518-4 v7
Bay control REC670
Application manual