1MRK 511 401-UUS F
Warning : If the calculated time to trip factor is below the setting Warning a warning signal is
activated. The setting is given in minutes.
8.8.3.1
Setting example
Calculation of the operate time with the available current is performed only if the calculated final
temperature is greater than the operate level temperature.
where:
t
operate
t
final
I
I
ref
I
operate
I
Bx
I
Trip
θ
n
Consider that the given system has
settings are used to calculate the operate time:
IRef
IBase1
IBase2
Tau1
Tau2
IHighTau1
Tau1High
ILowTau1
Tau1Low
IHighTau2
Tau2High
ILowTau2
Tau2Low
ITrip
ThetaInit
ResLo
Bay control REC670
Application manual
2
I
I
ref
2
I
I
Bx
ref
Trip
© Copyright 2017 ABB. All rights reserved
is the time to operate
is the time constant
is the steady state heat content
is the largest phase load current
is the given reference load current
is the operate level heat content
is the selected base current based cooling system
ON / OFF
is the operate level load current
is the current heat content
IBase of 1000 A and the cooling system is ON . The following
110%
110% of IB
120% of IB
150 min
90 min
110% of IB1
125% of tC1
90% of IB1
75% of tC1
110% of IB2
115% of tC2
90% of IB2
85% of tC2
120% of IBx
50%
60% of Itr
Section 8
Current protection
GUID-37AB7D3E-9380-49A4-A47D-067E3E5DC914 v1
179