ABB Relion 670 Series Applications Manual page 419

Bay control
Hide thumbs Also See for Relion 670 Series:
Table of Contents

Advertisement

1MRK 511 401-UUS F
15.1.3.2
Delta blocking scheme
Operation
Set
SchemeType
Set
Set
tCoord
tSendMin
Set
Unblock
Set
Set
tSecurity
DeltaI
Set
DeltaV
Set
Delta3I0
Set
Set
Delta3V0
15.1.3.3
Permissive underreaching scheme
Set
Operation
SchemeType
Set
tCoord
Set
tSendMin
Set
Set
Unblock
tSecurity
Set
15.1.3.4
Permissive overreaching scheme
Operation
Set
Scheme type
Set
tCoord
Set
Set
tSendMin
Unblock
Set
tSecurity
Set
15.1.3.5
Unblocking scheme
Unblock
Set
tSecurity
Set
Bay control REC670
Application manual
Enabled
=
DeltaBlocking
=
= 0 s
= 0 s
Disabled
=
NoRestart if Unblocking scheme with no alarm for loss of guard is
(Set to
to be used.
Set to
Restart if Unblocking scheme with alarm for loss of guard is to be
used)
= 0.035 s
= 10 %IB
= 5 %VB
= 10 %IB
= 5 %VB
=
Enabled
Permissive UR
=
= 0 ms
= 0.1 s
=
Disabled
= 0.035 s
Enabled
=
Permissive OR
=
= 0 ms
= 0.1 s (0 s in parallel line applications)
Disabled
=
= 0.035 s
Restart
=
(Loss of guard signal will give both trip and alarm
Choose
NoRestart if only trip is required)
= 0.035 s
© Copyright 2017 ABB. All rights reserved
Section 15
Scheme communication
GUID-F4359690-F433-46CB-A173-8C14559E3FCF v1
M13869-25 v4
M13869-34 v4
M13869-43 v4
413

Advertisement

Table of Contents
loading

This manual is also suitable for:

Rec670

Table of Contents