ABB Relion 670 Series Applications Manual page 111

Bay control
Hide thumbs Also See for Relion 670 Series:
Table of Contents

Advertisement

1MRK 511 401-UUS F
PHASORREPORT blocks have similar settings for SvcClass and ReportRate. Figure
settings for PMUREPORT function block demonstrated by PCM600 Parameter Setting Tool (PST).
IEC140000126 V2 EN-US
Figure 41: PMUREPORT settings in PCM600 PST
Figure
42
where two different SMAI blocks are connected to different PHASORREPORT blocks with different
instance numbers. In this example, as the PHASORREPORT blocks have different instance numbers
and different settings for SvcClass and ReportRate, a separate SMAI block is used for each
PHASORREPORT block.
IEC140000127 V2 EN-US
Figure 42: An example of correct connection of SMAI and PHASORREPORT blocks in ACT
Figure
43
where the same SMAI block is connected to different PHASORREPORT blocks with different
instance numbers. Such connection will be only correct if both connected PHASORREPORT blocks
have similar settings for SvcClass and ReportRate. If settings for PMUREPORT instances differ for
SvcClass or ReportRate, then PHASOR1 connection in PHASORREPORT1 instance 2 will not be
compliant with IEEE C37.118 standard. The reason is that the filtering in SMAI/3PHSUM block is
adapted according to the performance class (SvcClass) and reporting rate of the connected
instance of PHASORREPORT function block. In this example, SMAI1 will adapt its filtering
Bay control REC670
Application manual
shows an example of correct connection of SMAI and PHASORREPORT blocks in ACT
shows an example of wrong connection of SMAI and PHASORREPORT blocks in ACT
© Copyright 2017 ABB. All rights reserved
Wide area measurement system
41
shows the
IEC140000126-2-en.vsd
IEC140000127-2-en.vsd
Section 6
105