XRepTyp : Reporting type. Cyclic ( Cyclic ), magnitude deadband ( Dead band ), integral deadband ( Int
deadband ) or Deadband and xx se cyclic (xx: 5 sec, 30 sec, 1 min). The reporting interval is
controlled by the parameter
XDbRepInt : This setting handles all the reporting types. If setting is deadband in XRepTyp,
XDbRepInt defines the deadband in m% of the measuring range. For cyclic reporting type
XRepTyp : cyclic ), the setting value reporting interval is in seconds. Magnitude deadband is the
(
setting value in m% of measuring range. Integral deadband setting is the integral area, that is,
measured value in m% of measuring range multiplied by the time between two measured values.
XHiHiLim : High-high limit. Set as % of YBase (Y is SBase for S,P,Q UBase for Voltage measurement
IBase for current measurement).
and
XHiLim : High limit. Set as % of YBase (Y is SBase for S,P,Q UBase for Voltage measurement and
IBase for current measurement).
XLowLim : Low limit. Set as % of YBase (Y is SBase for S,P,Q UBase for Voltage measurement and
IBase for current measurement).
XLowLowLim : Low-low limit. Set as % of YBase (Y is SBase for S,P,Q UBase for Voltage
measurement and
XLimHyst : Hysteresis value in % of range and is common for all limits.
All phase angles are presented in relation to defined reference channel. The parameter
PhaseAngleRef defines the reference, see Section
Calibration curves
It is possible to calibrate the functions (CVMMXN, CMMXU, VMMXU and VNMMXU) to get class 0.5
presentations of currents, voltages and powers. This is accomplished by magnitude and angle
compensation at 5, 30 and 100% of rated current and voltage. The compensation curve will have
the characteristic for magnitude and angle compensation of currents as shown in figure
(example). The first phase will be used as reference channel and compared with the curve for
calculation of factors. The factors will then be used for all related channels.
Bay control REC670
Application manual
XDbRepInt .
IBase for current measurement).
© Copyright 2017 ABB. All rights reserved
"Analog
inputs".
Section 17
Monitoring
211
447