ABB Relion 670 Series Applications Manual page 302

Bay control
Hide thumbs Also See for Relion 670 Series:
Table of Contents

Advertisement

Section 14
Control
When a circuit breaker closing command is issued, the prepare three-pole output trip is set. When
issuing a circuit breaker closing command the
during that time, the auto recloser resets to the "Ready" state and the
first reclosing shot fails, a three-phase trip will be initiated and three-phase reclosing can follow, if
selected.
ARMode = 1/2ph , 1-phase or 2-phase reclosing in the first shot
14.2.2.10
At single-pole or two-pole tripping, the operation is as in the example described above, program
1/2/3ph . If the first reclosing shot fails, a three-pole trip will be issued and three-pole auto
mode
reclosing can follow, if selected. In the event of a three-pole trip,
will be inhibited and no auto reclosing takes place.
ARMode = 1ph+1*2ph, 1-phase or 2-phase reclosing in the first shot
14.2.2.11
At single-pole tripping, the operation is as in the above described example, program mode
1/2/3ph . The single-pole auto reclosing attempt can be followed by three-pole reclosing, if
selected. At two-pole trip, a failure of a two-pole auto reclosing attempt will inhibit the auto
recloser. No more shots are attempted. If the first trip is a three-pole trip, the auto-reclosing will
be inhibited. No more shots are attempted. The expression "1*2ph" should be understood as "Only
one shot at two-phase auto reclosing".
14.2.2.12
ARMode = 1/2ph + 1*3ph, 1-phase, 2-phase or 3-phase reclosing in the first
shot
At single-pole or two-pole tripping, the operation is as in the example described above, program
mode
1/2/3ph . If the first reclosing shot fails, a three-pole trip will be issued and three-pole
reclosing will follow, if selected. At three-pole trip, a failure of a three-pole auto reclosing attempt
will inhibit the auto recloser. No more shots are attempted. The expression "1*3ph" should be
understood as "Only one shot at three-pole auto reclosing".
ARMode = 1ph + 1*2/3ph, 1-phase, 2-phase or 3-phase reclosing in the first
14.2.2.13
shot
At single-pole or two-pole tripping, the operation is as in the above described example, program
1/2/3ph . If the first reclosing shot fails, a three-pole trip will be issued and three-pole
mode
reclosing will follow, if selected. At two-pole or three-pole trip a failure of a two-pole or three-pole
auto reclosing attempt will inhibit the auto recloser. No more shots are attempted. The expression
"1*2/3ph" should be understood as "Only one shot at two-pole or three-pole auto reclosing".
Table 33:
MODEINT (integer)
Table continues on next page
296
Type of reclosing shots at different settings of ARMode or integer inputs to MODEINT
ARMode
1
3ph
2
1/2/3ph
© Copyright 2017 ABB. All rights reserved
tReclaim timer is started. If no tripping takes place
TR3P input high, the auto recloser
Type of fault
1st shot
1ph
3ph
2ph
3ph
3ph
3ph
1ph
1ph
2ph
2ph
3ph
3ph
1MRK 511 401-UUS F
ACTIVE output resets. If the
M12391-136 v5
M12391-139 v5
GUID-9C2FB801-F324-465E-8FD2-715A9C3D0BD8 v2
M12391-146 v5
2nd-5th shot
3ph
3ph
3ph
3ph
3ph
3ph
Bay control REC670
Application manual