Pulse-counter logic (PCFCNT) function counts externally generated binary pulses, for instance
pulses coming from an external energy meter, for calculation of energy consumption values. The
pulses are captured by the binary input module (BIM), and read by the PCFCNT function. The
number of pulses in the counter is then reported via the station bus to the substation automation
system or read via the station monitoring system as a service value. When using IEC 61850–8–1, a
scaled service value is available over the station bus.
The normal use for this function is the counting of energy pulses from external energy meters. An
optional number of inputs from an arbitrary input module in IED can be used for this purpose with
a frequency of up to 40 Hz. The pulse-counter logic PCFCNT can also be used as a general purpose
counter.
18.1.3
Setting guidelines
Parameters that can be set individually for each pulse counter from PCM600:
Operation : Disabled / Enabled
tReporting : 0-3600s
EventMask : NoEvents / ReportEvents
Configuration of inputs and outputs of PCFCNT is made via PCM600.
On the Binary input module (BIM), the debounce filter default time is set to 1 ms, that is, the
counter suppresses pulses with a pulse length less than 1 ms. The input oscillation blocking
frequency is preset to 40 Hz meaning that the counter detects the input to oscillate if the input
frequency is greater than 40 Hz. Oscillation suppression is released at 30 Hz. Block/release values
for oscillation can be changed on the local HMI and PCM600 under Main menu/Configuration/I/O
modules.
Bay control REC670
Application manual
Metering
IEC 61850
identification
PCFCNT
© Copyright 2017 ABB. All rights reserved
IEC 60617
ANSI/IEEE C37.2
identification
device number
-
S00947 V1 EN-US
Section 18
Metering
IP14600-1 v3
M14879-1 v4
M13395-3 v6
M13396-4 v9
509

Advertisement

Table of Contents
loading

This manual is also suitable for:

Rec670

Table of Contents