Section 14
Control
Setting
TapChgBk
(manually reset
Table continues on next page
382
Values (Range)
Description
Alarm
If the input TCINPROG of TCMYLTC or TCLYLTC (84)
Auto Block
function block is connected to the tap changer
Auto&Man Block
mechanism, then this blocking condition will be active
if the TCINPROG input has not reset when the
tTCTimeout timer has timed out. The output TCERRAL
will be activated depending on the actual parameter
setting. In correct operation the TCINPROG shall
appear during the VRAISE/VLOWER output pulse and
disappear before the
This error condition can be reset by the input
RESETERR on TCMYLTC (84) function block, or
alternatively by changing control mode of TR1ATCC
(90) or TR8ATCC (90) function to Manual and then
back to Automatic.
© Copyright 2017 ABB. All rights reserved
tTCTimeout time has elapsed.
1MRK 511 401-UUS F
Bay control REC670
Application manual