Section 16
Logic
Name of input
IN14
IN15
IN16
The sum of the numbers in column "Value when activated" when all INx (where 1≤x≤16) are active
that is=1; is 65535. 65535 is the highest boolean value that can be converted to an integer by the
BTIGAPC function block.
16.10
Integer to Boolean 16 conversion IB16
16.10.1
Identification
Function description
Integer to boolean 16 conversion
16.10.2
Application
Integer to boolean 16 conversion function (IB16) is used to transform an integer into a set of 16
binary (logical) signals. It can be used – for example, to connect integer output signals from one
function to binary (logical) inputs to another function. IB16 function does not have a logical node
mapping.
The Boolean 16 to integer conversion function (IB16) will transfer a combination of up to 16 binary
inputs INx where 1≤x≤16 to an integer. Each INx represents a value according to the table below
from 0 to 32768. This follows the general formula: INx = 2
on the activated INx will be available on the output OUT as a sum of the values of all the inputs INx
that are activated. OUT is an integer. When all INx where 1≤x≤16 are activated that is = Boolean 1 it
corresponds to that integer 65535 is available on the output OUT. IB16 function is designed for
receiving up to 16 booleans input locally. If the BLOCK input is activated, it will freeze the output at
the last value.
Values of each of the different OUTx from function block IB16 for 1≤x≤16.
The sum of the value on each INx corresponds to the integer presented on the output OUT on the
function block IB16.
Name of input
IN1
IN2
IN3
IN4
Table continues on next page
436
Type
Default
BOOLEAN
0
BOOLEAN
0
BOOLEAN
0
IEC 61850
identification
IB16
Type
Default
BOOLEAN
0
BOOLEAN
0
BOOLEAN
0
BOOLEAN
0
© Copyright 2017 ABB. All rights reserved
Description
Value when
activated
Input 14
8192
Input 15
16384
Input 16
32768
IEC 60617
ANSI/IEEE C37.2
identification
device number
-
-
x-1
where 1≤x≤16. The sum of all the values
Description
Value when
activated
Input 1
1
Input 2
2
Input 3
4
Input 4
8
1MRK 511 401-UUS F
Value when
deactivated
0
0
0
SEMOD158367-1 v2
SEMOD167941-2 v2
SEMOD158499-5 v4
Value when
deactivated
0
0
0
0
Bay control REC670
Application manual