Section 22
Security
The list of internal events provides valuable information, which can be used during commissioning
and fault tracing.
The information can, in addition to be viewed on the built in HMI, also be retrieved with the aid of a
PC with PCM600 installed and by using the Event Monitoring Tool. The PC can either be connected
to the front port, or to the port at the back of the IED.
22.3
Change lock CHNGLCK
22.3.1
Application
Change lock function CHNGLCK is used to block further changes to the IED configuration once the
commissioning is complete. The purpose is to make it impossible to perform inadvertent IED
configuration and setting changes.
However, when activated, CHNGLCK will still allow the following actions that does not involve
reconfiguring of the IED:
Monitoring
Reading events
Resetting events
Reading disturbance data
Clear disturbances
Reset LEDs
Reset counters and other runtime component states
Control operations
Set system time
Enter and exit from test mode
Change of active setting group
The binary input controlling the function is defined in ACT or SMT. The CHNGLCK function is
configured using ACT.
LOCK
556
Binary input signal that will activate/deactivate the function, defined in ACT or SMT.
When CHNGLCK has a logical one on its input, then all attempts to modify the IED
configuration and setting will be denied and the message "Error: Changes blocked"
will be displayed on the local HMI; in PCM600 the message will be "Operation
denied by active ChangeLock". The CHNGLCK function should be configured so
that it is controlled by a signal from a binary input card. This guarantees that by
setting that signal to a logical zero, CHNGLCK is deactivated. If any logic is
included in the signal path to the CHNGLCK input, that logic must be designed so
that it cannot permanently issue a logical one to the CHNGLCK input. If such a
situation would occur in spite of these precautions, then please contact the local
ABB representative for remedial action.
© Copyright 2017 ABB. All rights reserved
1MRK 511 401-UUS F
GUID-B48775D0-ACF0-49C6-A7F6-69AF37F1C68F v1
GUID-51EEC9C7-8ECF-4546-BC26-326861654340 v4
GUID-8C333BC0-AA7A-4ED1-A772-18C22E8EEE62 v6
Bay control REC670
Application manual