ABB Relion 670 Series Applications Manual page 193

Bay control
Hide thumbs Also See for Relion 670 Series:
Table of Contents

Advertisement

1MRK 511 401-UUS F
No.
StartMode
12
LatchedStart
13
FollowStart
14
FollowStart
15
FollowStart
16
FollowStart&
Mode
17
FollowStart&
Mode
18
FollowStart&
Mode
No.
StartMode
FunctionMode = Current or CB Pos
19
LatchedStart
20
LatchedStart
Table continues on next page
Bay control REC670
Application manual
RetripMode
t1 and t2 initiated
with
Always
external START
Off
external START
UseFunctionM
external START
ode
Always
external START
Off
external START
and CBCLDLx
input has logical
value one
UseFunctionM
external START
ode
and CBCLDLx
input has logical
value one
Always
external START
and CBCLDLx
input has logical
value one
RetripMode
t1 and t2 initiated
with
Off
external START
UseFunctionM
external START
ode
© Copyright 2017 ABB. All rights reserved
When t1 has elapsed,
When t2 or t2MPh
TRRET will
has elapsed, TRBU
will be given if
always be given
CBCLDLx input has
logical value one
never be given
CBCLDLx input has
logical value one
be given if
CBCLDLx input has
CBCLDLx input has
logical value one
logical value one
if external START is
CBCLDLx input has
present
logical value one
never be given
be given if
CBCLDLx input has
logical value one
and external START
is present
be given if
be given if
CBCLDLx input has
CBCLDLx input has
logical value one
logical value one
and external START
and external START
is present
is present
be given if external
be given if
START is present
CBCLDLx input has
logical value one
and external START
is present
When t1 has elapsed,
When t2 or t2MPh
TRRET will
has elapsed, TRBU
will be given if
never be given
current is above set
level *) and higher
than I>BlkCBPos or
CBCLDLx input has
logical value one
when current is
smaller than
I>BlkCBPos
be given if current
current is above set
is above set level of
level *) and higher
IPh> and higher
than I>BlkCBPos or
than I>BlkCBPos or
CBCLDLx input has
CBCLDLx input has
logical value one
logical value one
when current is
when current is
smaller than
smaller than
I>BlkCBPos
I>BlkCBPos
Section 8
Current protection
t1 and t2 and t2MPh
will be stopped
(reset) if
t1 and (t2 or
t2MPh) and 150ms
expires and
CBCLDLx input has
logical value zero
external START
disappears
external START
disappears
external START
disappears
CBCLDLx input has
logical value zero
or external START
disappears
CBCLDLx input has
logical value zero
or external START
disappears
CBCLDLx input has
logical value zero
or external START
disappears
t1 and t2 and t2MPh
will be stopped
(reset) if
t1 and (t2 or
t2MPh) and 150ms
expires and
current is below
set level *) or
CBCLDLx input has
logical value zero
t1 and (t2 or
t2MPh) and 150ms
expires and
current is below
set level *) or
CBCLDLx input has
logical value zero
187