Section 8
Current protection
ANSI05000465 V2 EN-US
Figure 89: Typical connection for STBPTOC (50STB) in breaker-and-a-half arrangement.
8.10.3
Setting guidelines
The parameters for Stub protection STBPTOC (50STB) are set via the local HMI or PCM600.
The following settings can be done for the stub protection.
GlobalBaseSel : Selects the global base value group used by the function to define IBase , VBase and
SBase . Note that this function will only use IBase value.
Operation : Disabled / Enabled
EnableMode : This parameter can be set Enable or Continuous . With the Enable setting the function
is only active when a binary release signal ENABLE into the function is activated. This signal is
normally taken from an auxiliary contact (normally closed) of the line disconnector and connected
to a binary input ENABLE of the IED. With the setting
independent of presence of any external release signal.
IPickup : Current level for the Stub protection, set in % of IBase . This parameter should be set so
that all faults on the stub can be detected. The setting should thus be based on fault calculations.
t : Time delay of the operation. Normally the function shall be instantaneous.
8.11
Pole discrepancy protection CCPDSC(52PD)
190
© Copyright 2017 ABB. All rights reserved
Continuous the function is activated
1MRK 511 401-UUS F
M12909-3 v5