ABB Relion 670 Series Applications Manual page 455

Bay control
Hide thumbs Also See for Relion 670 Series:
Table of Contents

Advertisement

1MRK 511 401-UUS F
800/5 A
380kV 120V
/
3
ANSI09000039 V1 EN-US
Figure 212: Single line diagram for 380kV OHL application
In order to monitor, supervise and calibrate the active and reactive power as indicated in figure
it is necessary to do the following:
1.
Set correctly CT and VT data and phase angle reference channel
"Setting of the phase reference
2.
Connect, in PCM600, measurement function to three-phase CT and VT inputs
3.
Set under General settings parameters for the Measurement function:
Table 47:
Setting
Operation
PowAmpFact
PowAngComp
Mode
k
VGenZeroDb
IGenZeroDb
Table continues on next page
Bay control REC670
Application manual
380kV Busbar
kV
3
P
Q
380kV OHL
general settings as shown in table 47.
level supervision of active power as shown in table 48.
calibration parameters as shown in table 49.
General settings parameters for the Measurement function
Short Description
Operation Off/On
Amplitude factor to scale
power calculations
Angle compensation for phase
shift between measured I & U
Selection of measured current
and voltage
Low pass filter coefficient for
power measurement, V and I
Zero point clamping in % of
Ubase
Zero point clamping in % of
Ibase
© Copyright 2017 ABB. All rights reserved
IED
ANSI09000039-1-en.vsd
channel") using PCM600 for analog input channels
Selected
Comments
value
On
Function must be
1.000
It can be used during commissioning to achieve
higher measurement accuracy. Typically no scaling
is required
0.0
It can be used during commissioning to achieve
higher measurement accuracy. Typically no angle
compensation is required. As well here required
direction of P & Q measurement is towards
protected object (as per IED internal default
direction)
L1, L2, L3
All three phase-to-ground VT inputs are available
0.00
Typically no additional filtering is required
25
Set minimum voltage level to 25%. Voltage below
25% will force S, P and Q to zero.
3
Set minimum current level to 3%. Current below
3% will force S, P and Q to zero.
Section 17
Monitoring
PhaseAngleRef (see Section
On
212
449