ABB Relion 670 Series Applications Manual page 466

Bay control
Hide thumbs Also See for Relion 670 Series:
Table of Contents

Advertisement

Section 17
Monitoring
DirCoef : Directional coefficient for circuit breaker life calculation.
RatedOperCurr : Rated operating current of the circuit breaker.
RatedFltCurr : Rated fault current of the circuit breaker.
OperNoRated : Number of operations possible at rated current.
OperNoFault : Number of operations possible at rated fault current.
CBLifeAlmLevel : Alarm level for circuit breaker remaining life.
AccSelCal : Selection between the method of calculation of accumulated energy.
OperTimeDelay : Time delay between change of status of trip output and start of main contact
separation.
17.5
Event function EVENT
17.5.1
Identification
Function description
Event function
17.5.2
Application
When using a Substation Automation system with LON or SPA communication, time-tagged
events can be sent at change or cyclically from the IED to the station level. These events are
created from any available signal in the IED that is connected to the Event function (EVENT). The
EVENT function block is used for remote communication.
Analog, integer and double indication values are also transferred through the EVENT function.
17.5.3
Setting guidelines
The input parameters for the Event function (EVENT) can be set individually via the local HMI (Main
Menu/Settings / IED Settings / Monitoring / Event Function) or via the Parameter Setting Tool
(PST).
EventMask (Ch_1 - 16)
The inputs can be set individually as:
460
IEC 61850
identification
EVENT
© Copyright 2017 ABB. All rights reserved
IEC 60617
ANSI/IEEE C37.2
identification
device number
-
S00946 V1 EN-US
1MRK 511 401-UUS F
IP14590-1 v2
SEMOD167950-2 v2
M12805-6 v11
IP14841-1 v1
M12811-3 v3
M12811-5 v3
Bay control REC670