20.2.2
Setting guidelines
There are two settings related to the IEC 61850–8–1 protocol:
Operation : User can set IEC 61850 communication to Enabled or Disabled .
GOOSEPortEd1 : Selection of the Ethernet link where GOOSE traffic shall be sent and received. This
is only valid for Edition 1 and can be ignored if Edition 2 is used. For Edition 2, the Ethernet link
selection is done with the Ethernet Configuration Tool (ECT) in PCM600.
20.2.3
Horizontal communication via GOOSE
20.2.3.1
Sending data
In addition to the data object and data attributes of the logical nodes, it is possible to send the
outputs of the function blocks using the generic communication blocks. The outputs of this
function can be set in a dataset and be sent in a GOOSE Control Block to other subscriber IEDs.
There are different function blocks for different type of sending data.
Generic communication function for Single Point indication SPGAPC, SP16GAPC
Application
Generic communication function for Single Point Value (SPGAPC) function is used to send one
single logical output to other systems or equipment in the substation. SP16GAPC can be used to
send up to 16 single point values from the application functions running in the same cycle time.
SPGAPC has one visible input and SPGAPC16 has 16 visible inputs that should be connected in the
ACT tool.
Setting guidelines
There are no settings available for the user for SPGAPC.
Generic communication function for Measured Value MVGAPC
Application
Generic communication function for measured values (MVGAPC) function is used to send the
instantaneous value of an analog signal to other systems or equipment in the substation. It can
also be used inside the same IED, to attach a RANGE aspect to an analog value and to permit
measurement supervision on that value.
Setting guidelines
The settings available for Generic communication function for Measured Value (MVGAPC) function
allows the user to choose a deadband and a zero deadband for the monitored signal. Values within
the zero deadband are considered as zero.
The high and low limit settings provides limits for the high-high-, high, normal, low and low-low
ranges of the measured value. The actual range of the measured value is shown on the range
output of MVGAPC function block. When a Measured value expander block (RANGE_XP) is
connected to the range output, the logical outputs of the RANGE_XP are changed accordingly.
Bay control REC670
Application manual
© Copyright 2017 ABB. All rights reserved
Section 20
Station communication
SEMOD55317-5 v7
GUID-9888ECAD-8221-4B31-A443-EB1E3A9022C4 v1
SEMOD55999-1 v4
SEMOD55350-5 v8
SEMOD55376-5 v5
SEMOD55402-1 v3
SEMOD55872-5 v10
SEMOD55424-5 v5
521

Advertisement

Table of Contents
loading

This manual is also suitable for:

Rec670

Table of Contents