Figure 236: Example of a station configuration with the IED receiving analog values from
20.3.2
Faulty merging unit for bay in service
When a merging unit goes faulty while the bay is in service, the protection functions connected to
that merging unit get blocked. Also, protection functions configured in a 1 1/2 circuit breaker
applications, where two SV streams from different merging units are combined get blocked. Thus,
this has no effect on protection functions in a 1 1/2 circuit breaker configuration.
This can be resolved by connecting external binary input signals to the BLOCK input on the
respective SMAI function blocks with the use of ACT. When the BLOCK input on a SMAI function is
524
Station Wide
SCADA System
Other
Relays
CT
both classical measuring transformers and merging units.