ABB Relion 670 Series Applications Manual page 456

Bay control
Hide thumbs Also See for Relion 670 Series:
Table of Contents

Advertisement

Section 17
Monitoring
Setting
VBase (set in
Global base)
IBase (set in
Global base)
SBase (set in
Global base)
Table 48: Settings parameters for level supervision
Setting
PMin
PMax
PZeroDb
PRepTyp
PDbRepInt
PHiHiLim
PHiLim
PLowLim
PLowLowlLim
PLimHyst
Table 49: Settings for calibration parameters
Setting
IMagComp5
IMagComp30
IMagComp100
VAmpComp5
VMagComp30
VMagComp100
Table continues on next page
450
Short Description
Base setting for voltage level
in kV
Base setting for current level
in A
Base Setting for power base in
MVA
Short Description
Minimum value
Minimum value
Zero point clamping in 0.001%
of range
Reporting type
Cycl: Report interval (s), Db: In
0.001% of range, Int Db: In
0.001%s
High High limit (physical
value), % of SBase
High limit (physical value), in %
of SBase
Low limit (physical value), in %
of SBase
Low Low limit (physical value),
in % of SBase
Hysteresis value in % of range
(common for all limits)
Short Description
Magnitude factor to calibrate
current at 5% of In
Magnitude factor to calibrate
current at 30% of In
Magnitude factor to calibrate
current at 100% of In
Magnitude factor to calibrate
voltage at 5% of Vn
Magnitude factor to calibrate
voltage at 30% of Vn
Magnitude factor to calibrate
voltage at 100% of Vn
© Copyright 2017 ABB. All rights reserved
Selected
Comments
value
400.00
Set rated OHL phase-to-phase voltage
1000
Set rated primary CT current used for OHL
1000
Set based on rated Power
Selected
Comments
value
-100
Minimum expected load
100
Maximum expected load
3000
Set zero point clamping to 60 MW that is, 3% of
200 MW
db
Select magnitude deadband supervision
2000
Set ±Δdb=40 MW that is, 2% (larger changes than
40 MW will be reported)
60
High alarm limit that is, extreme overload alarm,
hence it will be 415 MW.
50
High warning limit that is, overload warning, hence
it will be 371 MW.
-50
Low warning limit -500 MW
-60
Low alarm limit -600 MW
1
Set ±Δ Hysteresis 20 MW that is, 1% of range
(2000 MW)
Selected
Comments
value
0.00
0.00
0.00
0.00
0.00
0.00
1MRK 511 401-UUS F
Bay control REC670
Application manual