ABB Relion 670 Series Applications Manual page 577

Bay control
Hide thumbs Also See for Relion 670 Series:
Table of Contents

Advertisement

1MRK 511 401-UUS F
23.12.1.1
IEC 61850 protocol test mode
The function block TESTMODE has implemented the extended testing mode capabilities for IEC
61850 Ed2 systems. Operator commands sent to the function block TESTMODE determine the
behavior of the functions. The command can be given remotely from an IEC 61850 client or from
the LHMI under the Main menu/Test/Function test modes/Communication/Station
Communication/IEC61850 LD0 LLN0/LD0LLN0:1. The possible values of the function block
TESTMODE are described in
There is no setting in PCM600 via PST for the TESTMODE function block.
The DataObject Mod of the Root LD.LNN0 can be set on the LHMI under Main menu/Test/
Function test modes/Communication/Station communication/IEC61850 LD0 LLN0/LD0LLN0:1
On , Off , TestBlocked , Test or Blocked .
to
When the setting of the DataObject Mod is changed at this level, all Logical Nodes inside the
logical device update their own behavior according to IEC61850-7-4. The supported values of the
function block TESTMODE are described in
When the function block TESTMODE is in test mode the Start LED on the LHMI is turned on with
steady light.
The parameter
Function test modes/Communication/Station Communication
The parameter Mod can be set on the LHMI to the same values as for the DataObject Mod of the
Root LD.LNN0 to
test modes/ Differential protection/GeneratorDiff(87G,3Id/I>)/ GENPDIF(87G,3Id/I>):1.
It is possible that the behavior of the function block TESTMODE is also influenced by other sources
as well, independent of the mode communicated via the IEC61850-8-1 station bus. For example the
insertion of the test handle into the test switch with its auxiliary contact is connected to a BI on
the IED and further inside the configuration to the input IED_TEST on the function block
TESTMODE. Another example is when loss of Service Values appears, or as explained above the
setting via the LHMI.
When setting via PST or LHMI the parameter
function is not executed and the behavior (beh) is set to
When a behavior of a function is
current state.
Bay control REC670
Application manual
Communication protocol manual, IEC 61850 Edition 1 and Edition 2 .
To be able to set the function block TESTMODE remotely, the setting via path on
LHMI and in PST: Main menu/Configuration/Communication/ Station
Communication/IEC61850-8-1/IEC61850-8-1:1
Off . The possible values of the parameter RemoteModControl are Off ,
to
Maintenance or All levels . The Off value denies all access to function block
TESTMODE from remote,
Maintenance and All levels allow any orCat.
(orCat) is
Mod of any specific function block can be configured under Main menu/Test/
On , Off , TestBlocked , Test or Blocked . For Example, Main menu/ Test/ Function
Off the function will not execute. The related Mod keeps its
When IEC 61850 Mod of a function is set to
LHMI will be set to flashing to indicate the abnormal operation of the IED.
© Copyright 2017 ABB. All rights reserved
RemoteModControl may not be set
Maintenance requires that the category of the originator
Communication protocol manual, IEC 61850 Edition 2 .
Operation of any function in an IED is set to Off , the
Off and it is not possible to override it.
Off or Blocked , the Start LED on the
Section 23
Basic IED functions
GUID-82998715-6F23-4CAF-92E4-05E1A863CF33 v5
571