In many busbar arrangements such as breaker-and-a-half, ring breaker, mesh corner, there will be
a T-feeder from the current transformer at the breakers up to the current transformers in the
feeder circuit (for example, in the transformer bushings). It is often required to separate the
protection zones that the feeder is protected with one scheme while the T-zone is protected with
a separate differential protection scheme. The 1Ph high impedance differential HZPDIF (87)
function in the IED allows this to be done efficiently, see Figure 53.
Bay control REC670
Application manual
That the settings of U>Alarm, U>Trip and SeriesResistor must be chosen such that
both U>Alarm/SeriesResistor and U>Trip/SeriesResistor are >4% of IRated of the
used current input. Normally the settings shall also be such that U>Alarm/
SeriesResistor and U>Trip/SeriesResistor both gives a value <4*IRated of the used
current input. If not, the limitation in how long time the actual current is allowed to
persist not to overload the current input must be considered especially during the
secondary testing.
© Copyright 2017 ABB. All rights reserved
Section 7
Differential protection
M16850-4 v7
123