1MRK 511 401-UUS F
tStartMove is the supervision time for the apparatus to start moving after a command execution
is done from the SCSWI function. When the time has expired, the command supervision is reset,
and a cause-code is given.
During the
state. When the time has expired, the command supervision is reset, and a cause-code is given.
The indication of the mid-position at SCSWI is suppressed during this time period when the
position changes from open to close or vice-versa if the parameter
the SCSWI function.
In most cases, the same value can be used for both
function. However,
delays, mainly when representing a circuit breaker.
14.3.8.5
Bay Reserve (QCRSV)
The timer
be done by requesting bay due to for example communication failure.
When the parameter
apparatus (x) in the bay, only the own bay is reserved, that is, the output for reservation request of
other bays (RES_BAYS) will not be activated at selection of apparatus x.
14.3.8.6
Reservation input (RESIN)
With the
in the SA system.
14.4
Interlocking (3)
The main purpose of switchgear interlocking is:
To avoid the dangerous or damaging operation of switchgear
To enforce restrictions on the operation of the substation for other reasons for example, load
configuration. Examples of the latter are to limit the number of parallel transformers to a
maximum of two or to ensure that energizing is always from one side, for example, the high
voltage side of a transformer.
This section only deals with the first point, and only with restrictions caused by switching devices
other than the one to be controlled. This means that switch interlock, because of device alarms, is
not included in this section.
Disconnectors and grounding switches have a limited switching capacity. Disconnectors may
therefore only operate:
With basically zero current. The circuit is open on one side and has a small extension. The
capacitive current is small (for example, < 5A) and power transformers with inrush current are
not allowed.
To connect or disconnect a parallel circuit carrying load current. The switching voltage across
the open contacts is thus virtually zero, thanks to the parallel circuit (for example, < 1% of
rated voltage). Paralleling of power transformers is not allowed.
Bay control REC670
Application manual
tIntermediate time, the position indication is allowed to be in an intermediate (00)
tStartMove may need to be increased to accommodate for the communication
tCancelRes defines the supervision time for canceling the reservation, when this cannot
ParamRequestx ( x =1-8) is set to Only own bay res. individually for each
FutureUse parameter set to Bay future use the function can handle bays not yet installed
© Copyright 2017 ABB. All rights reserved
SuppressMidPos is set to On in
tStartMove and tIntermediate as in the source
Section 14
Control
M16677-3 v3
M16678-3 v3
IP15572-1 v2
M13530-4 v4
327