ABB Relion 670 Series Applications Manual page 67

Bay control
Hide thumbs Also See for Relion 670 Series:
Table of Contents

Advertisement

1MRK 511 401-UUS F
ANSI05000462 V1 EN-US
Figure 10: Example how to set CT_WyePoint parameters in the IED
Bay control REC670
Application manual
Transformer
Transformer and
Line protection
Setting of current input
for transformer functions:
for transformer functions:
Set parameter
CT_WyePoint with
Transformer as
reference object.
Correct setting is
"ToObject"
© Copyright 2017 ABB. All rights reserved
Setting of current input
Set parameter
CT_WyePoint with
Transformer as
reference object.
Correct setting is
"ToObject"
Analog inputs
Line
Reverse
Forward
Definition of direction for
directional
line functions
Setting of current input
for line functions:
Set parameter
CT_WyePoint with
Line as
reference object.
Correct setting is
"FromObject"
en05000462_ansi.vsd
Section 4