Precision Time Protocol (PTP) is enabled/disabled using the Ethernet configuration tool /ECT) in
PCM600.
PTP can be set to On , Off or Slave only . When set to Slave only the IED is connected to the PTP-
group and will synchronize to the grandmaster but cannot function as the grandmaster.
A PTP-group is set up by connecting the IEDs to a network and enabling PTP. To set one IED as the
grandmaster change Priority2 to 127 instead of the default 128.
IEC16000089 V1 EN-US
Figure 254: Enabling PTP in ECT
PTP VLAN tag must have the same value in station clock and in the IED. The default value is set
The
to 0.
The
PTP VLAN tag does not need to be the same on all access points in one IED. It is possible to
mix as long as they are the same for all devices on each subnet.
Bay control REC670
Application manual
Set the course time synchronizing source (
time synchronization of line differential function is used. Set the fine time
synchronization source (
complete time synchronization. GPS alone shall synchronize the analogue values in
such systems.
All protection functions will be blocked if the AppSynch parameter is set to Synch
while there is no 9-2 synchronization source. For more information please refer to
the "IEC/UCA 61850-9-2LE communication protocol" section.
© Copyright 2017 ABB. All rights reserved
CoarseSyncSrc ) to Disabled when GPS
FineSyncSource ) to GPS . The GPS will thus provide the
Section 23
Basic IED functions
GUID-424227EC-74A1-4628-8948-C1876840ABFE v3
IEC16000089-1-en.vsdx
575