Section 14
Control
For IEC 61850-8-1 communication, the Bay Control function can be set to discriminate between
commands with orCat station and remote (2 and 3). The selection is then done through the IEC
61850-8-1 edition 2 command LocSta.
QCBAY also provides blocking functions that can be distributed to different apparatuses within
the bay. There are two different blocking alternatives:
Blocking of update of positions
Blocking of commands
IEC13000016 V2 EN-US
Figure 128: APC - Local remote function block
14.3.3
Switch controller SCSWI
SCSWI may handle and operate on one three-phase device or three one-phase switching devices.
After the selection of an apparatus and before the execution, the switch controller performs the
following checks and actions:
316
© Copyright 2017 ABB. All rights reserved
1MRK 511 401-UUS F
IEC13000016-2-en.vsd
Bay control REC670