tPoleDiscord is the allowed time to have discrepancy between the poles at control of three single-
phase breakers. At discrepancy an output signal is activated to be used for trip or alarm, and
during a command, the control function is reset, and a cause-code is given.
SuppressMidPos when On suppresses the mid-position during the time tIntermediate of the
connected switches.
The parameter
operate, Sel & Op phase, or only at operate, Op phase.
14.3.8.3
Switch (SXCBR/SXSWI)
tStartMove is the supervision time for the apparatus to start moving after a command execution
is done from the SCSWI function. When the time has expired, the command supervision is reset,
and a cause-code is given.
During the
state. When the time has expired, the command supervision is reset, and a cause-code is given.
The indication of the mid-position at SCSWI is suppressed during this time period when the
position changes from open to close or vice-versa if the parameter
the SCSWI function.
If the parameter
correct end position is reached. If the parameter is set to
remains active until the timer
tOpenPulse is the output pulse length for an open command. If AdaptivePulse is set to Adaptive , it
is the maximum length of the output pulse for an open command. The default length is set to 200
ms for a circuit breaker (SXCBR) and 500 ms for a disconnector (SXSWI).
tClosePulse is the output pulse length for a close command. If AdaptivePulse is set to Adaptive , it
is the maximum length of the output pulse for an open command. The default length is set to 200
ms for a circuit breaker (SXCBR) and 500 ms for a disconnector (SXSWI).
14.3.8.4
Proxy for signals from switching device via GOOSE XLNPROXY
SwitchType setting controls the evaluation of the operating capability. If SwitchType is set to
The
Circuit Breaker , the input OPCAP is interpreted as a breaker operating capability, otherwise it is
interpreted as a switch operating capability.
Table 37:
Value
1
2
3
4
5
6
7
326
InterlockCheck decides if interlock check should be done at both select and
tIntermediate time, the position indication is allowed to be in an intermediate (00)
AdaptivePulse is set to Adaptive the command output pulse resets when a new
tOpenPulsetClosePulse has elapsed.
Operating capability values for breaker/switches
Breaker operating capability, CbOpCap
None
Open
Close – Open
Open – Close – Open
Close – Open – Close – Open
Open – Close – Open – Close – Open
more
© Copyright 2017 ABB. All rights reserved
SuppressMidPos is set to On in
Not adaptive the command output pulse
Switch operating capability, SwOpCap
None
Open
Close
Close and Open
Larger values handled as 4, both Close and Open
1MRK 511 401-UUS F
M16675-3 v8
GUID-7C253FE7-6E02-4F94-96C7-81C9129D925D v1
Bay control REC670
Application manual