ABB Relion 670 Series Applications Manual page 347

Bay control
Hide thumbs Also See for Relion 670 Series:
Table of Contents

Advertisement

1MRK 511 401-UUS F
14.4.5
Interlocking for bus-section breaker A1A2_BS (3)
14.4.5.1
Application
The interlocking for bus-section breaker (A1A2_BS ,3) function is used for one bus-section circuit
breaker between section 1 and 2 according to figure 147. The function can be used for different
busbars, which includes a bus-section circuit breaker.
ANSI04000516 V1 EN-US
Figure 147: Switchyard layout A1A2_BS (3)
The signals from other bays connected to the module A1A2_BS are described below.
14.4.5.2
Signals from all feeders
If the busbar is divided by bus-section circuit breakers into bus-sections and both circuit breakers
are closed, the opening of the circuit breaker must be blocked if a bus-coupler connection exists
between busbars on one bus-section side and if on the other bus-section side a busbar transfer is
in progress:
(WA1)A1
(WA2)B1
(WA7)C
ABC_LINE
ANSI04000489 V1 EN-US
Figure 148: Busbars divided by bus-section circuit breakers
To derive the signals:
Bay control REC670
Application manual
WA1 (A1)
189
189G
152
389G
A1A2_BS
Section 1
A1A2_BS
B1B2_BS
ABC_BC
AB_TRAFO
© Copyright 2017 ABB. All rights reserved
WA2 (A2)
289
289G
489G
en04000516_ansi.vsd
Section 2
ABC_BC
ABC_LINE
AB_TRAFO
en04000489_ansi.vsd
A2
B2
C
Section 14
Control
IP14154-1 v2
M15110-3 v7
M15111-4 v3
M15111-6 v4
341

Advertisement

Table of Contents
loading

This manual is also suitable for:

Rec670

Table of Contents