Section 17
Monitoring
When an input is set, the respective output is set for a user defined time. If the input signal
remains set for a longer period, the output will remain set until the input signal resets.
INPUTn
OUTPUTn
IEC09000732 V1 EN-US
Figure 217: BINSTATREP logical diagram
17.7.3
Setting guidelines
The pulse time
can be set or reset individually, but the pulse time will be the same for all outputs in the entire
BINSTATREP function.
17.8
Fault locator LMBRFLO
17.8.1
Identification
Function description
Fault locator
17.8.2
Application
The main objective of line protection and monitoring IEDs is fast, selective and reliable operation
for faults on a protected line section. Besides this, information on distance to fault is very
important for those involved in operation and maintenance. Reliable information on the fault
location greatly decreases the downtime of the protected lines and increases the total availability
of a power system.
The fault locator is started with the input CALCDIST to which trip signals indicating in-line faults
are connected, typically distance protection zone 1 and accelerating zone or the line differential
protection. The disturbance report must also be started for the same faults since the function
uses pre- and post-fault information from the trip value recorder function (TVR).
Beside this information the function must be informed about faulted phases for correct loop
selection (phase selective outputs from differential protection, distance protection, directional OC
protection, and so on). The following loops are used for different types of faults:
for 3 phase faults: loop A-B.
for 2 phase faults: the loop between the faulted phases.
for 2 phase-to-ground faults: the loop between the faulted phases.
for phase-to-ground faults: the phase-to-ground loop.
468
t
t is the only setting for the Logical signal status report (BINSTATREP). Each output
IEC 61850
identification
LMBRFLO
© Copyright 2017 ABB. All rights reserved
t
IEC09000732-1-en.vsd
IEC 60617
ANSI/IEEE C37.2
identification
device number
-
-
1MRK 511 401-UUS F
GUID-BBDA6900-4C1A-4A7C-AEA5-3C49C2749254 v2
IP14592-1 v2
M14892-1 v3
M13752-3 v6
Bay control REC670
Application manual