ABB Relion 670 Series Applications Manual page 532

Bay control
Hide thumbs Also See for Relion 670 Series:
Table of Contents

Advertisement

Section 20
Station communication
20.3.4
Setting guidelines
Merging Units (MUs) have several settings on local HMI under:
Main menu/Configuration/Analog modules/MUx:92xx. The corresponding settings are also
available in PST (PCM600).
Main menu/Configuration/Communication/Merging units configuration/MUx:92xx. The
corresponding settings are also available in ECT (PCM600).
XX can take value 01–12.
20.3.4.1
Specific settings related to the IEC/UCA 61850-9-2LE communication
The process bus communication IEC/UCA 61850-9-2LE has specific settings, similar to the analog
inputs modules.
If there are more than one sample group involved, time synch is mandatory. If there is no time
synchronization, the protection functions will be blocked due to condition blocking.
CTStarPointx : These parameters specify the direction to or from object. See also section
of current
SyncLostMode : If this parameter is set to Block and the IED hardware time synchronization is lost
or the synchronization to the MU time is lost, the protection functions in the list
due to conditional blocking. If this parameter is set to
in list
""
MU time is lost or the IED has lost global common synchronization (i.e. GPS, IRIG-B or PTP).
output will be set if IED hardware time synchronization is lost.
either of MU or IED hardware time synchronization is lost.
Table 67:
Function description
Accidental energizing
protection for
synchronous generator
Broken conductor check
Capacitor bank protection
Pole discordance
protection
Breaker failure protection
Breaker failure protection,
single phase version
Table continues on next page
526
channels".
are blocked if the IED hardware time synchronization is lost or the synchronization of the
Binary signals over LDCM are transmitted as valid and processed normally even
when analog signals are transmitted as invalid due to loss of communication or
loss of time synchronization.
Blocked protection functions if IEC/UCA 61850-9-2LE communication is interrupted and functions are
connected to specific MUs
IEC 61850 identification
AEGPVOC
BRCPTOC
CBPGAPC
CCPDSC
CCRBRF
CCSRBRF
© Copyright 2017 ABB. All rights reserved
BlockOnLostUTC , the protection functions
MUSYNCH output will be set if
Function description
Two step overvoltage
protection
Four step single phase
overcurrent protection
Radial feeder protection
Instantaneous phase
overcurrent protection
PoleSlip/Out-of-step
protection
Restricted earth fault
protection, low
impedance
1MRK 511 401-UUS F
GUID-29B296B3-6185-459F-B06F-8E7F0C6C9460 v4
SEMOD166590-24 v7
"Setting
""
will be blocked
SYNCH
IEC 61850 identification
OV2PTOV
PH4SPTOC
PAPGAPC
PHPIOC
PSPPPAM
REFPDIF
Bay control REC670
Application manual