Figure 107: Application of VDSPVC
13.3.3
Setting guidelines
The parameters for Fuse failure supervision VDSPVC are set via the local HMI or PCM600.
The voltage input type (phase-to-phase or phase-to-neutral) is selected using
ConTypePilot parameters, for main and pilot fuse groups respectively.
The settings
VBase . Set VBase to the primary rated phase-to-phase voltage of the potential voltage
transformer.
group, that is used by VDSPVC (60), is set by the setting parameter
Bay control REC670
Application manual
The connection type for the main and the pilot fuse groups must be consistent.
Vdif Main block , Vdif Pilot alarm and VSealIn are in percentage of the base voltage,
VBase is available in the Global Base Value groups; the particular Global Base Value
© Copyright 2017 ABB. All rights reserved
A
B
C
Main Vt circuit
IED
FuseFailSupvn
ANSI12000143-1-en.vsd
Secondary system supervision
GUID-0D5A517C-1F92-46B9-AC2D-F41ED4E7C39E v1
GUID-52BF4E8E-0B0C-4F75-99C4-0BCB22CDD166 v2
GUID-0B298162-C939-47E4-A89B-7E6BD7BEBB2C v2
ConTypeMain and
GlobalBaseSel .