ABB Relion 670 Series Applications Manual page 446

Bay control
Hide thumbs Also See for Relion 670 Series:
Table of Contents

Advertisement

Section 16
Logic
RefSource : This setting is used to select the reference source between input and setting for
comparison.
Input REF : The function will take reference value from input REF
Set Value : The function will take reference value from setting SetValue
SetValue : This setting is used to set the reference value for comparison when setting RefSource is
selected as
16.13.4
Setting example
For absolute comparison between inputs:
Set the
EnaAbs = Absolute
RefSource = Input REF
Set the
Similarly for Signed comparison between inputs
EnaAbs = Signed
Set the
RefSource = Input REF
Set the
For absolute comparison between input and setting
EnaAbs = Absolute
Set the
RefSource = Set Value
Set the
SetValue shall be set between -2000000000 to 2000000000
Similarly for signed comparison between input and setting
EnaAbs = Signed
Set the
RefSource = Set Value
Set the
SetValue shall be set between -2000000000 to 2000000000
16.14
Comparator for real inputs - REALCOMP
16.14.1
Identification
Function description
Comparator for real inputs
440
SetValue .
IEC 61850
identification
REALCOMP
© Copyright 2017 ABB. All rights reserved
IEC 60617
ANSI/IEEE C37.2
identification
device number
Real<=>
1MRK 511 401-UUS F
GUID-13302FD6-1585-42FE-BD6D-44F231982C59 v2
GUID-0D68E846-5A15-4C2C-91A2-F81A74034E81 v1
Bay control REC670
Application manual