Error code
(Hexadecimal)
1BA3H
1BA4H
1BA5H
1BA6H
1BA7H
1BA8H
1BA9H
1BAAH
1BABH
1BACH
1BAEH
Downloaded from
ManualsNet.com
Error name
Error details and causes
Software stroke limit lower
In the unit of "degree", the setting value of the detailed
limit
parameter 1 "Software stroke limit lower limit value" is
outside the setting range.
[Operation status at error occurrence]
The READY signal [X0] is not turned ON.
Software stroke limit lower
In a unit other than "degree", the software stroke limit
limit
upper limit value is smaller than the setting value of the
software stroke limit lower limit value.
[Operation status at error occurrence]
The READY signal [X0] is not turned ON.
Software stroke limit
• The setting value of the detailed parameter 1 "[Pr.14]
selection
Software stroke limit selection" is outside the setting
range.
• In the unit of "degree", "1: Apply software stroke limit
on machine feed value" is set.
[Operation status at error occurrence]
The READY signal [X0] is not turned ON.
Software stroke limit valid/
The setting value of the detailed parameter 1 "[Pr.15]
invalid setting
Software stroke limit valid/invalid setting" is outside the
setting range.
[Operation status at error occurrence]
The READY signal [X0] is not turned ON.
Command in-position width
The setting value of the detailed parameter 1 "[Pr.16]
Command in-position width" is outside the setting
range.
[Operation status at error occurrence]
The READY signal [X0] is not turned ON.
Illegal torque limit setting
The setting value of the detailed parameter 1 "[Pr.17]
value
Torque limit setting value" is outside the setting range.
[Operation status at error occurrence]
The READY signal [X0] is not turned ON.
M code ON timing error
The setting value of the detailed parameter 1 "[Pr.18] M
code ON signal output timing" is outside the setting
range.
[Operation status at error occurrence]
The READY signal [X0] is not turned ON.
Speed switching mode error
The setting value of the detailed parameter 1 "[Pr.19]
Speed switching mode" is outside the setting range.
[Operation status at error occurrence]
The READY signal [X0] is not turned ON.
Interpolation speed
The setting value of the detailed parameter 1 "[Pr.20]
designation method error
Interpolation speed designation method" is outside the
setting range.
[Operation status at error occurrence]
The READY signal [X0] is not turned ON.
Current value update request
The setting value of the detailed parameter 1 "[Pr.21]
error
Feed current value during speed control" is outside the
setting range.
[Operation status at error occurrence]
The READY signal [X0] is not turned ON.
Speed-position function
The detailed parameter 1 "[Pr.81] Speed-position
selection error
function selection" is preset to 2 and the following three
conditions are not satisfied:
• Unit is "degree".
• Software stroke limits are invalid.
• Update feed current value.
[Operation status at error occurrence]
The READY signal [X0] is not turned ON.
search engine
Remedy
Correct the setting value, turn the PLC READY
signal [Y0] from OFF to ON.
In a unit other than "degree", configure the
setting so that "[Pr.13] Software stroke limit
lower limit value" is smaller than "[Pr.12]
Software stroke limit upper limit value", turn the
PLC READY signal [Y0] from OFF to ON.
• Bring the setting into the setting range.
• In the unit of "degree", set "0: Apply software
stroke limit on feed current value".
Correct the setting value, turn the PLC READY
signal [Y0] from OFF to ON.
Correct the setting value, turn the PLC READY
signal [Y0] from OFF to ON.
Correct the setting value, turn the PLC READY
signal [Y0] from OFF to ON.
Correct the setting value, turn the PLC READY
signal [Y0] from OFF to ON.
Correct the setting value, turn the PLC READY
signal [Y0] from OFF to ON.
Correct the setting value, turn the PLC READY
signal [Y0] from OFF to ON.
Correct the setting value, turn the PLC READY
signal [Y0] from OFF to ON.
• Speed-position switching control (ABS mode)
should satisfy the conditions given on the left.
• When speed-position switching control (ABS
mode) is not to be exercised, set 0 to speed-
position function selection and turn the PLC
READY signal [Y0] from OFF to ON.
14 TROUBLESHOOTING
14.5 List of Error Codes