Error code
1E53H
1E60H
1E61H
1E62H
1E63H
1E70H
1E71H
1E72H
1E73H
1E74H
1E75H
1E76H
14 TROUBLESHOOTING
650
14.5 List of Error Codes
Downloaded from
ManualsNet.com
Error name
Error details and causes
Speed change gear overflow
Overflow (sign reversion) occurred in input values,
because the speed change ratio of speed change gear
is too large.
[Operation status at error occurrence]
Synchronous control is immediately stopped.
Outside cam No. range
The synchronous parameter "[Pr.440] Cam No." is set
to a value other than 0 to 256.
[Operation status at error occurrence]
Synchronous control does not start.
Cam not registered
The cam data of the cam No. specified in the
synchronous parameter "[Pr.440] Cam No." does not
exist on the Cam open area.
[Operation status at error occurrence]
Synchronous control does not start.
Cam axis length per cycle
The synchronous parameter "[Pr.439] Cam axis length
outside range
per cycle" is set to 0 or lower.
[Operation status at error occurrence]
Synchronous control does not start.
Outside output axis
The synchronous parameter "[Pr.447] Output axis
smoothing time constant
smoothing time constant" is set to a value other than 0
range
to 5000.
[Operation status at error occurrence]
Synchronous control does not start.
Outside setting method of
The synchronous parameter "[Pr.460] Setting method
current value per cycle after
of current value per cycle after main shaft gear" is set
main shaft gear range
to a value other than 0 to 2.
[Operation status at error occurrence]
Synchronous control does not start.
Outside current value per
The synchronous parameter "[Pr.465] Current value
cycle after main shaft gear
per cycle after main shaft gear (Initial setting)" is set to
(Initial setting) range
a value other than 0 to (Cam axis length per cycle - 1).
[Operation status at error occurrence]
Synchronous control does not start.
Outside setting method of
The synchronous parameter "[Pr.461] Setting method
current value per cycle after
of current value per cycle after auxiliary shaft gear" is
auxiliary shaft gear range
set to a value other than 0 to 2.
[Operation status at error occurrence]
Synchronous control does not start.
Outside current value per
The synchronous parameter "[Pr.466] Current value
cycle after auxiliary shaft
per cycle after auxiliary shaft gear (Initial setting)" is set
gear (Initial setting) range
to a value other than 0 to (Cam axis length per cycle -
1).
[Operation status at error occurrence]
Synchronous control does not start.
Outside cam axis position
The synchronous parameter "[Pr.462] Cam axis
restoration object range
position restoration object" is set to other than 0 to 2.
[Operation status at error occurrence]
Synchronous control does not start.
Outside setting method of
The synchronous parameter "[Pr.463] Setting method
cam reference position range
of cam reference position" is set to a value other than 0
to 2.
[Operation status at error occurrence]
Synchronous control does not start.
Outside setting method of
• The synchronous parameter "[Pr.464] Setting
cam axis current value per
method of cam axis current value per cycle" is set to
cycle range
a value other than 0 to 3.
• "3: Current value per cycle after auxiliary shaft gear"
is established when the auxiliary shaft does not
exist.
[Operation status at error occurrence]
Synchronous control does not start.
search engine
Remedy
• Set a smaller absolute value for the
synchronous parameter "[Pr.436] Speed
change ratio: Numerator".
• Set a larger value for the synchronous
parameter "[Pr.437] Speed change ratio:
Denominator".
• Decrease the input axis speed.
Set a value within the range of 0 to 256.
Specify the cam No. of an existing cam data.
Set a value within the range of 1 to 2147483647.
Set a value within the range of 0 to 5000.
Set a value within the range of 0 to 2.
Set within the range of 0 to (Cam axis length per
cycle - 1).
Set a value within the range of 0 to 2.
Set within the range of 0 to (Cam axis length per
cycle - 1).
Set a value within the range of 0 to 2.
Set a value within the range of 0 to 2.
• Set a value within the range of 0 to 3.
• Set other than "3: Current value per cycle after
auxiliary shaft gear" when the auxiliary shaft
does not exist.