Invalidqt Function Block - Hitachi Relion 650 Series Technical Manual

Hide thumbs Also See for Relion 650 Series:
Table of Contents

Advertisement

Section 11
Logic
Settings
Table 129: RSMEMORYQT Group settings (basic)
Name
Memory
11.1.2.10

INVALIDQT function block

Identification
Function description
INVALIDQT function block
Function which sets the quality flag of binary signals to invalid according to a "valid" input.
Inputs are copied to outputs. If input VALID is 0, or if its quality invalid bit is set, all outputs invalid
quality bit will be set. The timestamp of an output will be set to the latest timestamp of INPUT and
VALID input.
Function block
INPUT1
INPUT2
INPUT3
INPUT4
INPUT5
INPUT6
INPUT7
INPUT8
INPUT9
INPUT10
INPUT11
INPUT12
INPUT13
INPUT14
INPUT15
INPUT16
VALID
IEC09000305 V1 EN-US
Figure 70:
Signals
Table 130: INVALIDQT Input signals
Name
INPUT1
INPUT2
INPUT3
INPUT4
INPUT5
INPUT6
INPUT7
Table continues on next page
132
Values (Range)
Unit
Off
-
On
INVALIDQT
OUTPUT1
OUTPUT2
OUTPUT3
OUTPUT4
OUTPUT5
OUTPUT6
OUTPUT7
OUTPUT8
OUTPUT9
OUTPUT10
OUTPUT11
OUTPUT12
OUTPUT13
OUTPUT14
OUTPUT15
OUTPUT16
IEC09000305-1-en.vsd
INVALIDQT function block
Type
BOOLEAN
BOOLEAN
BOOLEAN
BOOLEAN
BOOLEAN
BOOLEAN
BOOLEAN
© 2021 Hitachi Energy. All rights reserved.
Step
Default
-
On
IEC 61850
IEC 60617
identification
identification
INVALIDQT
Default
Description
0
Indication input 1
0
Indication input 2
0
Indication input 3
0
Indication input 4
0
Indication input 5
0
Indication input 6
0
Indication input 7
1MRK 511 557-UEN Rev. A
Description
Operating mode of the memory function
GUID-F84B0F9A-5536-4E57-854C-9C9C5EED1FA1 v1
ANSI/IEEE C37.2
device number
-
-
GUID-8496F960-8E7B-40DA-B574-745B68E31946 v2
GUID-BDE95E52-D073-4216-B68E-8095B79C6C44 v2
PID-1188-SETTINGS v15
PID-1106-INPUTSIGNALS v9
Technical Manual