Function Block; Signals - Hitachi Relion 650 Series Technical Manual

Hide thumbs Also See for Relion 650 Series:
Table of Contents

Advertisement

Section 14
Basic IED functions
GUID-C857FBD9-F449-465A-B27F-EF0F684CCAC7 V1 EN-US
Figure 177: One-and-a-half breaker scheme in a substation
This function is specific to PWC600. It takes the instantaneous sample and RMS values from two 3-
phase sources as inputs. Based on the source selector setting, it provides the same signals from the
selected source as outputs to the receiving functions. The function also provides a blocking output,
which can be used for blocking other functions while re-synchronizing to the selected source.
14.12.3

Function block

BLOCK
BLOCK
BLOCK
BLKFUNC
BLKFUNC
BLKFUNC
AI3P1
AI3P1
AI3P1
AI3P2
AI3P2
AI3P2
GUID-E53AC69C-CF01-4B8F-84C4-F5A75E9B933E V2 EN-US
Figure 178: ACT view of 3PHSELECT function block
14.12.4

Signals

Table 379: 3PHSELECT Input signals
Name
BLOCK
BLKFUNC
AI3P1
AI3P2
400
Source1
CB‐1
CT‐1
CT‐2
CB‐2
CT‐3
CB‐3
Source 2
3PHSELECT
3PHSELECT
BLOCKOUT
BLOCKOUT
BLOCKOUT
AI3P
AI3P
AI3P
AI1
AI1
AI1
AI2
AI2
AI2
AI3
AI3
AI3
AIN
AIN
AIN
IEC19000271‐2-en.vsd.vsdx
Type
Default
BOOLEAN
0
BOOLEAN
0
GROUP
-
SIGNAL
GROUP
-
SIGNAL
© 2021 Hitachi Energy. All rights reserved.
PT‐1
PT‐2
Feeder 1
Feeder 2
PT‐3
PT‐4
IEC19000270‐1‐en.vsdx
Description
Block input for blocking binary outputs
Block the function from providing any outputs
Group signal for input from Source 1
Group signal for input from Source 2
1MRK 511 557-UEN Rev. A
GUID-05892E6E-0D4A-4B40-A3EE-D025A57068B8 v2
PID-7274-INPUTSIGNALS v1
Technical Manual

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Switchsync pwc600

Table of Contents