Inrush Current Peak Evaluation; Electrical Status Of Load; Operation Count Monitoring - Hitachi Relion 650 Series Technical Manual

Hide thumbs Also See for Relion 650 Series:
Table of Contents

Advertisement

Section 12
Monitoring
ABLSUMRLX
IECEQUATION19399 V1 EN-US
Activating the RESETABL input will set ABLSUM to the initial value InitialCumAbl; ABLSUMRLX will
be updated accordingly.
12.18.7.15

Inrush current peak evaluation

Starting from activation of the Close command input CLCMDINP, ACBMSCBR searches for the
current sample (from I3PL input) having the highest absolute value within 15 power cycles. To filter
out high-frequency transients, only sets of four consecutive samples exceeding the threshold level
defined by InrushCurRef are considered. The signed sample value is published as inrush current
peak at the INRUSHPLX output.
This evaluation is done only for transformer loads.
12.18.7.16

Electrical status of load

As soon as the load voltage or current RMS received by the function (through I3PL or U3PL) crosses
a pre-defined open coarse threshold value (absolute value of OpenCThreshold), then binary output
LOADONLX gets activated and remains active as long as it satisfies the condition.
Similarly, as soon as the load voltage or current RMS received by the function (through I3PL or
U3PL) falls below a pre-defined open fine threshold value (absolute value of OpenFThreshold), then
binary output LOADOFFLX gets activated and remains active as long as it satisfies the condition.
The above-mentioned points for different scenarios are summarized in
Table 280: Activation of LOADONLX and LOADOFFLX outputs
Feedback
SigO
None
None
None
Load
voltage
Load
voltage
Load
voltage
Current
Current
Current
12.18.7.17

Operation count monitoring

With the monitoring of actual operations, the function also counts the number of CB operations. For
that purpose, a cycle of CB closing and CB opening is considered as one operation. The function
presents output(OPRCNTRST) to accommodate the count of Close and Open cycles operations.
308
ABLSUMLX
=
AblationAlarmLevel
Iload(RMS)
Iload(RMS) ≥
≥OpenCThreshold
OpenFThreshol
*IBase
d *IBase
X
X
X
X
X
X
X
X
X
X
X
X
N
N
N
Y
Y
X
© 2021 Hitachi Energy. All rights reserved.
Table
Uload(RMS) ≥
Uload(RMS) ≥
OpenCThresho
OpenFThreshold
ld *UBase*
*UBase*
ScaleFactorV
ScaleFactorV
N
N
N
Y
Y
X
N
N
N
Y
Y
X
X
X
X
X
X
X
1MRK 511 557-UEN Rev. A
GUID-0CE13C44-355A-4264-9612-5ED76A30F78A v1
GUID-1A12A0E7-661E-4252-A406-B2DEEA9C081A v1
280.
LOADON
LOADOF
LX
FLX
0
1
0
0
1
0
0
1
0
0
1
0
0
1
0
0
1
0
GUID-600C84B4-35BC-4DF0-A553-18B9C1F937D8 v3
Technical Manual